Off-Grid Battery Bank Sizing: A Step-by-Step Guide

How to size the battery bank for an off-grid inverter system — daily capacity, depth of discharge, days of autonomy and a worked example for a typical home.

Sizing GuideOff-GridBattery

Battery banks are the most expensive part of an off-grid system and the easiest to get wrong. Size them too small and the system cuts out early on cloudy days; too large and you pay for capacity you rarely use.

The sizing formula

Battery capacity (Ah) = daily energy (Wh) ÷ battery voltage (V) ÷ depth of discharge (%)

Three variables drive the result:

  1. Daily energy use (Wh/day) — from your load audit (see our solar panel sizing guide)
  2. Battery voltage (V) — 12 V, 24 V or 48 V, matching your inverter
  3. Depth of discharge (DoD) — the usable portion of the battery

Depth of discharge matters

Different chemistries allow different discharge depth:

Battery typeSafe DoDNotes
Lead-acid (flooded)50%Regular topping charge needed
Lead-acid (AGM / gel)50–60%Maintenance-free, moderate cost
LiFePO480–90%Longer life, higher upfront cost

Worked example

Continuing the home from our sizing guide:

  • Daily load: 2,160 Wh
  • Inverter / system voltage: 48 V
  • Battery type: LiFePO4 at 85% DoD
  • Desired autonomy (no sun): 2 days

Step 1 — energy per day the battery must store: 2,160 Wh ÷ 0.85 = 2,541 Wh of usable capacity

Step 2 — with 2 days of autonomy: 2,541 × 2 = 5,082 Wh

Step 3 — capacity in amp-hours at 48 V: 5,082 Wh ÷ 48 V = 106 Ah

A practical choice: a 48 V, 100 Ah (≈ 5 kWh) LiFePO4 bank, or two parallel 100 Ah packs if you want more margin.

Matching the inverter

  • Pick an inverter whose DC input voltage matches the bank (12/24/48 V).
  • Keep the bank’s charge current within the MPPT controller’s rating — a 5 kWh bank usually charges at 40–60 A comfortably.
  • LiFePO4 banks need a BMS with communication (CAN/RS485) where the inverter supports it, so charging stops correctly.

Our off-grid inverters support 12 V, 24 V and 48 V banks (selected models also 60 V and 72 V) — the specification table on each product page lists the DC input range.

To run the capacity, inverter and array numbers together instead of one at a time, use our off-grid system sizing calculator — it applies the depth-of-discharge figures from the table above and suggests matching catalog models for the system voltage you pick.

Battery sizing — FAQ

How many days of autonomy should I design for?

Two to three days of autonomy is typical for a home with generator backup; three to five for remote sites where no backup exists. More autonomy means more batteries and more cost.

Can I mix battery types in one bank?

No. Mixing chemistries or ages causes imbalance, uneven charging and premature failure. Replace the whole bank or expand with identical packs.

Do I need a bigger battery for a bigger inverter?

Not directly. Inverter size follows peak load; battery size follows daily energy and autonomy. Match both to the same system voltage so they work together.